'use strict'; // To de done: // - CheckLID status (should be open or closed) // - Is it necessary to switch the bias-voltage off? // - Get reasonable timeouts for all steps (wait, get, run) // - Improve order to accelerate execution // // ================================================================= /* var table = [ [ "AGILENT_CONTROL" ], [ "BIAS_CONTROL" ], [ "CHAT" ], [ "DATA_LOGGER" ], [ "DRIVE_CONTROL" ], [ "FEEDBACK" ], [ "FAD_CONTROL" ], [ "FSC_CONTROL" ], [ "FTM_CONTROL" ], [ "LID_CONTROL" ], [ "MAGIC_WEATHER" ], [ "MCP" ], [ "PWR_CONTROL" ], [ "RATE_CONTROL" ], [ "RATE_SCAN" ], [ "SMART_FACT" ], [ "TIME_CHECK" ], [ "TNG_WEATHER" ], ]; if (dim.state("DRIVE_CONTROL").name=="Locked") { throw new Error("Drivectrl still locked... needs UNLOCK first."); //while (!dim.send("DRIVE_CONTROL")) // v8.sleep(); //dim.send("DRIVE_CONTROL/UNLOCK"); //dim.wait("DRIVE_CONTROL", "Armed", 1000); } */ console.out(""); dim.alarm(); var loop; include("scripts/Handler.js"); include("scripts/CheckStates.js"); // ----------------------------------------------------------------- // Make sure camera electronics is switched on and has power // ----------------------------------------------------------------- include("scripts/handleAgilentPowerOn.js"); include("scripts/handlePwrCameraOn.js"); checkSend(["AGILENT_CONTROL","PWR_CONTROL"]); loop = new Handler("PowerOn"); //loop.add(handleAgilentPowerOn); loop.add(handlePwrCameraOn); loop.run(); console.out(""); // If power was switched on: wait for a few seconds // ----------------------------------------------------------------- // Now take care that the bias control, the ftm and the fsc are // properly connected and are in a reasonable state (e.g. the // trigger is switched off) // ----------------------------------------------------------------- include("scripts/handleBiasVoltageOff.js"); include("scripts/handleFtmIdle.js"); include("scripts/handleFscConnected.js"); include("scripts/handleFeedbackConnected.js"); include("scripts/handleRatectrlConnected.js"); include("scripts/handleLidClosed.js"); include("scripts/handleFadConnected.js"); checkSend(["BIAS_CONTROL","FAD_CONTROL","FTM_CONTROL", "FSC_CONTROL", "FEEDBACK", "RATE_CONTROL", "MCP"]); dim.send("MCP/RESET"); loop = new Handler("SystemSetup"); loop.add(handleBiasVoltageOff); loop.add(handleFtmIdle); loop.add(handleFscConnected); loop.add(handleFadConnected); loop.add(handleFeedbackConnected); // Feedback needs FAD to be Connected loop.add(handleRatectrlConnected); //loop.add(handleLidClosed); loop.run(); console.out("biasctrl: "+dim.state("BIAS_CONTROL").name); console.out("ftmctrl: "+dim.state("FTM_CONTROL").name); console.out("fscctrl: "+dim.state("FSC_CONTROL").name); console.out("feedback: "+dim.state("FEEDBACK").name); console.out("ratecontrol: "+dim.state("RATE_CONTROL").name); console.out("fadctrl: "+dim.state("FAD_CONTROL").name); console.out("mcp: "+dim.state("MCP").name); console.out(""); console.out("Enable all FTU"); dim.send("FTM_CONTROL/ENABLE_FTU", -1, true); // ----------------------------------------------------------------- // Now we check the FTU connection // ----------------------------------------------------------------- /* include("scripts/handleFtuCheck.js"); loop = new Handler("FtuCheck"); loop.ftuList = new Subscription("FTM_CONTROL/FTU_LIST"); loop.add(handleFtuCheck); loop.run(); loop.ftuList.close(); dim.log("All FTUs are enabled and without error."); */ console.out("Checking FTU: start"); include("scripts/CheckFTU.js"); console.out("Checking FTU: done"); console.out(""); // ----------------------------------------------------------------- // Now we check the clock conditioner // ----------------------------------------------------------------- var sub_counter = new Subscription("FTM_CONTROL/COUNTER"); var counter = sub_counter.get(3000, false).counter; dim.send("FTM_CONTROL/REQUEST_STATIC_DATA"); v8.timeout(3000, function() { if (sub_counter.get(0, false).counter>counter) return true; }); if (sub_counter.get(0, false).qos&0x100==0) throw new Error("Clock conditioner not locked."); sub_counter.close(); // ----------------------------------------------------------------- // Now we can safely try to connect the FAD boards. // ----------------------------------------------------------------- /* include("scripts/handleFadConnected.js"); // If FADs already connected checkSend(["FAD_CONTROL"]); loop = new Handler("ConnectFad"); loop.add(handleFadConnected); loop.run(); var failed = false; dim.onchange["FAD_CONTROL"] = function(arg) { if (this.rc && arg.name!="Connected") failed = true; } console.out("FADs connected."); console.out(""); console.out(dim.state("FAD_CONTROL").name); console.out(dim.state("MCP").name); */ // ================================================================ // Underflow check // ================================================================ // Is it necessary to check for the so called 'underflow-problem'? // (This is necessary after each power cycle) // ---------------------------------------------------------------- include('scripts/CheckUnderflow.js'); // Now it is time to check the connection of the FADs // it might hav thrown an exception already anyway // ================================================================ // Power on drive system if power is off (do it hre to make sure not // everything is switchd on at the same time) // ================================================================ //console.out("PWR: "+(dim.state("PWR_CONTROL").index&16)); if ((dim.state("PWR_CONTROL").index&16)==0) { console.out("Drive cabinet not power... Switching on."); dim.send("PWR_CONTROL/TOGGLE_DRIVE"); v8.timeout(5000, function() { if (dim.state("PWR_CONTROL").index&16) return true; }); } include("scripts/handleDriveArmed.js"); checkSend(["DRIVE_CONTROL"]); loop = new Handler("ArmDrive"); loop.add(handleDriveArmed); loop.run(); // ================================================================ // Bias crate calibration // ================================================================ // Bias crate calibration if necessary (it is aftr 4pm (local tome) // and the last calibration was more than eight hours ago. // ----------------------------------------------------------------- // At this point we know that: // 1) The lid is closed // 2) The feedback is stopped // 3) The voltage is off function makeCurrentCalibration() { dim.send("BIAS_CONTROL/SET_ZERO_VOLTAGE"); dim.wait("BIAS_CONTROL", "VoltageOff", 30000); // waS: 15000 var now = new Date(); dim.send("FEEDBACK/CALIBRATE"); console.out("Wait for calibration to start"); dim.wait("FEEDBACK", "Calibrating", 5000); console.out("Wait for calibration to end"); dim.wait("FEEDBACK", "Calibrated", 90000); console.out("Calibration finished ["+(new Date()-now)+"ms]"); console.out("Wait for voltage to be off"); dim.wait("BIAS_CONTROL", "VoltageOff", 30000); // was: 15000 } // Check age of calibration var service_calibration = new Subscription("FEEDBACK/CALIBRATION"); var data_calibration = service_calibration.get(3000, false); var age = data_calibration.time; var now = new Date(); var diff = (now-age)/3600000; var fb_state = dim.state("FEEDBACK").index; // !data_calibration.data: FEEDBACK might just be freshly // started and will not yet serve this service. if (fb_state<5 || (diff>8 && now.getHours()>16)) { if (fb_state<5) console.out("No BIAS crate calibration available: New calibration needed."); else console.out("Last BIAS crate calibration taken at "+age.toUTCString()+": New calibration needed."); makeCurrentCalibration(); } service_calibration.close(); // ================================================================ // Crosscheck all states // ================================================================ // FIXME: Check if there is a startup shceduled, if not do not force // drive to be switched on var table = [ [ "TNG_WEATHER" ], [ "MAGIC_WEATHER" ], [ "CHAT" ], [ "SMART_FACT" ], [ "TEMPERATURE" ], [ "DATA_LOGGER", [ "NightlyFileOpen", "WaitForRun", "Logging" ] ], [ "FSC_CONTROL", [ "Connected" ] ], [ "MCP", [ "Idle" ] ], [ "TIME_CHECK", [ "Valid" ] ], [ "PWR_CONTROL", [ "SystemOn" ] ], [ "AGILENT_CONTROL", [ "VoltageOn" ] ], [ "BIAS_CONTROL", [ "VoltageOff" ] ], [ "FEEDBACK", [ "Calibrated" ] ], [ "RATE_SCAN", [ "Connected" ] ], [ "RATE_CONTROL", [ "Connected" ] ], [ "LID_CONTROL", [ "Open", "Closed" ] ], [ "DRIVE_CONTROL", [ "Armed", "Tracking", "OnTrack", "Locked" ] ], [ "FTM_CONTROL", [ "Valid", "TriggerOn" ] ], [ "FAD_CONTROL", [ "Connected", "WritingData" ] ], ]; if (!checkStates(table)) { throw new Error("Something unexpected has happened. Although the startup-"+ "procedure has finished, not all servers are in the state "+ "in which they ought to be. Please, try to find out what "+ "happened..."); }