Changeset 12728


Ignore:
Timestamp:
12/20/11 14:27:13 (13 years ago)
Author:
kraehenb
Message:
Added bias reconnect at the beginning and fixed the bug that the dark count run was taken while the bias is ramping (added waiting for bias state 5 and back to 9).
File:
1 edited

Legend:

Unmodified
Added
Removed
  • trunk/FACT++/ScriptsForDimCtrl/FirstDrsCalib

    r12680 r12728  
    22.! echo `date -u` "First DRS Calibration Script starting up..." >> ~/FACT++/ScriptsForDimCtrl/DataTaking.log
    33.! echo `date -u` "-------------------------------------------" >> ~/FACT++/ScriptsForDimCtrl/DataTaking.log
     4BIAS_CONTROL/RECONNECT
     5FEEDBACK/START_TEMP_CONTROL 0.00
    46FEEDBACK/ENABLE_OUTPUT 1
    57BIAS_CONTROL/SET_ZERO_VOLTAGE
     
    3638BIAS_CONTROL/SET_GLOBAL_DAC 1
    3739.s BIAS_CONTROL 9
     40.s BIAS_CONTROL 5
     41.s BIAS_CONTROL 9
    3842.! echo `date -u` "... done" >> ~/FACT++/ScriptsForDimCtrl/DataTaking.log
    3943