wiki:TroubleShootingBias

Version 7 (modified by ftemme, 11 years ago) ( diff )

--

back to TroubleShooting

Trouble Shooting - Bias

bias disconnection

Symptom

  • biasctrl is in state DISCONNECTED

Solution

  • Do _RECONNECT_
  • Send a command like _REQUEST_STATUS_
  • Sometime the bias crate will disconnect again, do _RECONNECT_

Not Helping

  • do not close or kill biasctrl

Overcurrent Status

Symptom

  • when biasctrl ramped the voltage, it get in the state OVERCURRENT

Solution

  • First try biasctrl/RESET_OVER_CURRENT_STATUS (maybe a few times)
  • if it don't help try to ramp the voltage down
    • biasctrl/SET_GLOBAL_DAC 0

Not Helping

  • do not close or kill biasctrl

Status notReferenced

Symptom

  • biasctrl is in state notReferenced

Solution

  • start the Ramping again
    • biasctrl/START

Not Helping

  • do not close or kill biasctrl
Note: See TracWiki for help on using the wiki.