= after a power cut = == restart hardware == - contact the MAGIC shift crew to switch '''gate''' back on [[BR]] - email adress of the MAGIC shifters: {{{magic_shifters@mpp.mpg.de}}} [[BR]] - phone numbers for MAGIC shift crew: [http://www.magic.iac.es/contacts/], login with user "FACT" and the usual password [[BR]] - go to [https://trac.fact-project.org/wiki/TroubleShootingComputers%20] and switch the other computers back on in the given order [[BR]] - '''IMPORTANT''': it might be that "Raid Pwr1" has to be switched on '''BEFORE''' newdaq can boot [[BR]] - TODO: second raid? [http://10.0.100.232/]? where to be switched back on? [[BR]] - '''before you do any software trouble shooting''': go to [http://10.0.100.100/] to check if the pump is working, the bias power is enabled and the cooling liquid flow meter is measuring enough throughput. In case some of it aren't, go to [http://10.0.100.232/] and switch BIAS, LID and PUMP back on. Go to [http://10.0.100.100/] to switch the camera back on. [[BR]] == restart software == - now the software has to be restarted according to ([https://trac.fact-project.org/wiki/TroubleShootingSoftware%20]) [[BR]] - version for dummies (you can quit the screen session with Ctrl+a and d): [[BR]] 1) ssh fact@newdaq [[BR]] 2) screen -x => will probably say "There is no screen to be attached". [[BR]] 3) screen -c /home/fact/.screenrc_newdaq [[BR]] 4) ssh fact@gate [[BR]] 5) screen -x => will probably say "There is no screen to be attached". [[BR]] 6_A) /users needs to be mounted, 'sudo mount -a' [[BR]] 6_B) screen -c /users/fact/.screenrc_gate [[BR]] 7) ssh fact@aux [[BR]] 8) screen -x => will probably say "There is no screen to be attached". [[BR]] 9) screen -c /home/fact/.screenrc_aux [[BR]] 10) (still on aux) ps aux | grep vnc => if no vnc is running => vncserver :1 [[BR]] 11) use a software like vinagre to log into the newly created vnc session: vinagre aux:1 [[BR]] 12) to start the tpoint camera gui, in a terminal: cd /home/fact/Drive.new/FACT++ and then ./tpoint [[BR]] - check in smartfact [http://fact-project.org/smartfact], whether the systems are all in a correct state (lid closed, fad control connected, etc.) - if not, send the corresponding commands in the screen session on newdaq == IMPORTANT == In case the telescope was operated while the power cut happened => make sure the telescope gets parked manually (TODO: link) '''if the observation should not be continued!!!!'''