Observation Limits
| value | max | action |
| Zenith angle | ~88° | reschedule |
| median current per pixel in camera | 115 uA | reschedule or stop |
| maximum current in a single pixel | 160 uA | reschedule or stop |
| Clouds | no stars visible in pointing direction | reschedule or stop |
| abs(T_GAPD - T_ambient) | 15° C | stop |
| T_container | 40° C | stop |
| Wind speed | 50km/h | stop |
| Rain | stop | |
| water on mirrors | stop |
"stop or reschedule"?
- reschedule
- In case it seems possible to observe another source, the shifter is free to try that.
Also sometimes SpecialMeasurements can be done.
- stop
-
Stop the normal observation mode, by scheduling the task named
Sleepon the scheduler page for right now. This brings the system into a safe state.
ToDo
- Explain how to check currents for alternative sources using smartfact.
- Apply a filter to the wind speed, in order to convert the condition "significantly or in regular intervals" into a simple yes/no decision. And integral filter would maybe do, it converts "significantly" or "regularly" into a similar answer depending on the time constant of course.